Operating values

Dosing inputs

Edit any value. Results update instantly.

LIVE INPUTS
mg/L
Target chemical dose in the treatment stream.
m³/hr
Worksheet operating reference: 100–280 m³/hr.
%
As defined in your Excel calculator (% × 10 = g/L).
Calculated solution concentration50.60 g/L
Calculated output

Pump requirement

Based on your latest calibration readings.

Within range
Required pump setting
51.97/ 100 scale
Calibrated setting for current dosing conditions.
Pump rate
1,014.49mL/min
Pump rate
60.87L/hr
Soda required
3,080g/hr
Soda required
3.08kg/hr
Pump setting is within the configured maximum.
Formula basis: mL/min = (dose in mg/L × flow in m³/hr) ÷ (strength % × 10) × 1,000 ÷ 60.